15.2 TRIAC

Background
A defective Triac is detected, when a current of more than 500mA is measured for more than 5 seconds in a switched off channel, and the main conductor is on. In this case a message with the measured current is added to the event journal and the channel is set on error. The main conductor is switched off to protect attached equipment. Operation after such an event is only possible if the error is cleared and the main conductor is switched on again. If the error persists the Triac has to be exchanged, or the channel load has to be removed. In this case an operation of the device using only the remaining channels is possible.

NOTE

Triac used: BTA26-800

Replacement procedure