9.1.3 Control

For how the control loop works and what the output level is, see Section 6.1, “Control loop and output level”; the operating modes are explained in Section 6.2, “Operating modes”.

REG-00 Control

Display of the abbreviation for the selected operating mode with setpoint.

REG-01 Operating mode

Select the operating mode of the channel.

REG-02 Temperature setpoint

Enter the set temperature. It is effective in the operating modes “Temperature” and “Monitor” – in the latter it does not control but is the reference for the temperature monitoring.

Unit °C · Range -350.0…999.9 · Factory setting 200.0 · from #3 Master

REG-03 Nominal output level

Enter the ratio setpoint. Only effective with operating mode “Manual ratio”.

Unit % · Range 0…100 · Factory setting 100 · from #3 Master

REG-04 Maximum output

The power consumption cannot exceed this value. This limitation applies for all operating modes. This is useful for oversized heaters, for instance.

Unit % · Range 0…100 · Factory setting 100 · from #3 Master

REG-05 Apply output level

The current output level is adopted as the new setpoint for the manual output operating mode.

from #1 Operator

REG-06 Follow channel

Channel number of the channel that is followed regardless of its own values.

Factory setting 0 · from #3 Master

REG-07 Follow factor

Entering a factor unequal 1,0 decreases or increases the power of the channel relative to the following channel accordingly.

Range 0.01…15.0 · Factory setting 1.0 · from #3 Master