The main contactor can be switched on and off via this menu. The fields above the buttons show whether the contactor may switch on and whether it really is on; a tick means “yes” in each case. What the contactor symbol in the upper menu bar shows is explained at the end of this section.
How the fields depend on each other is shown by the ladder diagram below. A rung conducts only if every contact in it is closed; a contact with a slash is a break contact, the circle at the end is a coil. The main contactor therefore pulls in only if all boards release, the operator switches it on and the external circuit is closed.

Figure 26: The release of the main contactor as a ladder diagram. The feedback measures the voltage ahead of the coil, not the position of the contactor contacts.
The contactor symbol in the upper menu bar shows command and feedback in a single sign. It is red as soon as the contactor is commanded or its coil is live, and crossed out as long as the coil has no voltage. A red, crossed-out flash therefore means: commanded, but not switched on. If the state cannot be determined, a red exclamation mark appears, see FAQ-05, “Contactor symbols”.
| Symbol | Appearance | Command (target) | Feedback (actual) | Meaning |
|---|---|---|---|---|
| Flash crossed out, white | Off | Off | Normal state. The device is safely switched off. | |
| Flash filled, red | On | On | Normal state. The device is active and the feedback confirms it. | |
| Flash crossed out, red | On | Off | Discrepancy. The contactor does not pick up despite the command – usually the safety circuit is open. To investigate, see FAQ-06, “Contactor does not pick up”. | |
| Flash outline, red | Off | On | Critical fault. The contactor coil is live although the software commands “off” – the relay on the display board is welded, or the coil is fed externally. Take the device out of service and notify customer service. |
WARNING
When the main contactor is switched on, voltage can be applied to the tool connector at any time!Before switching on, the device asks for confirmation: “Switch on main contactor?” Only the confirmation applies voltage. The prompt also appears when switching on is triggered from another operating path — at the end of the Wizard, for example.