MSG-91 Contactor off! Reason: External Safety Circuit

Cause: The main contactor was commanded on but did not report back that it had switched on – four seconds after switching on or later during operation. “Boards OK” was set; the device therefore attributes the interruption to the external safety circuit and has withdrawn the command by itself.
Measure: Check the external safety circuit and the emergency stop. If the connection is not used, the bridge X100 pin 3 to pin 4 has to be fitted. If the circuit is closed, notify customer service. To investigate, see FAQ-06, “Contactor does not pick up”.