The Thermonom monitors the temperature of every channel in three mutually independent ways. They serve different purposes, and they differ in what they trigger.
| Stage | Reference | Reaction |
|---|---|---|
| Warning band | relative to the setpoint | Warning. The channel keeps heating and counts as not operational. |
| Temperature limit | absolute | Error. The channel switches off and stays off until the error is acknowledged. |
| Sensor diagnosis | measuring signal | Error with an adjustable reaction – switch off, follow, hold or manual output mode. |

Figure 21: Up to the marker the channel is heating up – it lies below the warning band but reports no alarm. Only after that is a deviation a deviation alarm, here the excursion upwards.
The warning limit is a distance from the setpoint, 10 K ex works, and applies equally upwards and downwards. If the actual temperature leaves this band, the channel is no longer operational – this already applies while heating up, because a channel at half temperature lies far below the band.
A deviation alarm only arises from this once the channel has previously reached its setpoint, that is has been inside the band for at least two seconds. This distinction is the reason why a normal heat-up does not produce a flood of alarms, while a drop during operation is noticed immediately.
What the band indicates is usually not a sensor problem but a thermal one:
This limit protects the tool and the material, not the control. It is entered per channel as an absolute temperature, 600 °C ex works. If the actual temperature exceeds it for longer than three seconds, the Thermonom triggers an error and switches the channel off.
Two properties are important:
NOTICE
Set the temperature limit to a value that the material and the tool can withstand – not to the highest one the device permits. The factory setting of 600 °C is above the decomposition temperature of most plastics; it protects the device, not the production.A thermocouple can become unusable in several ways, and the Thermonom distinguishes them because the remedy differs:
| Finding | Meaning and remedy |
|---|---|
| Sensor break | No continuous measuring circuit – cable detached, connector not plugged in, thermocouple broken. The channel cannot be operated under temperature control. |
| Sensor polarity | The measured value runs downwards while heating: the two wires have been swapped. Instead of rewiring, the polarity can be reversed in the channel settings. |
| Sensor short circuit | The wires touch each other in front of the measuring point. The sensor then delivers a plausible but wrong value – usually too cold. This is detected by the fact that a lot of energy has flowed into the channel over a longer period without the temperature having risen. |
NOTE
The short circuit detection is switched off ex works. It infers from the ratio of energy introduced to temperature rise – with very sluggish tools this inference can be wrong and switch off an intact channel. If you switch it on, watch the behaviour during the first heat-up.What is to happen in the event of a sensor fault can be set: switch off, follow another channel, hold the last output level, or change to manual output mode with the nominal output level. The last three keep production going, see Section 6.10, “Groups, substitution and failures”.
WARNING
With the reactions “Hold” and “Manual output” the channel keeps heating without temperature measurement. There is then no monitoring that could detect overheating – not even the absolute temperature limit, because it lacks the measured value. Only use these settings on channels whose heating power matches the zone, and watch the channel afterwards.Related settings:TFL-05, “Temp. warning limit” · TFL-06, “Temperature alarm” · TFL-07, “In case of errors…” · TFL-10, “Sensor short detection”