FAQ-06 I switch on but the contactor does not pick up. How do I find the cause?
Open the control dialog. It shows three things side by side:
If the feedback differs from the command for more than four seconds, the device withdraws the command by itself. That is not a fault but the safety function – it prevents the device from switching permanently against an open safety circuit.
If all releases and “Boards OK” are set and the feedback still fails to appear, the external release or emergency-stop circuit is open. Check whether the emergency stop and all integrated switches have released. If the connection is not used it has to be bridged; in the factory state it is (display board, X100, pin 3 to pin 4). If “Boards OK” is missing, see FAQ-07, “Boards OK missing”.
WARNING
Before opening the device, the mains plug must be pulled out and the absence of voltage checked! Work on this connection is part of the electrical installation of the plant and may only be carried out by a qualified electrician.Keywords: Main contactor, Diagnostics, Safety circuit, Feedback